Schneider LRD340 TeSys Deca Thermal Overload Relay – 30…40 A
₨ 26,000
₨ 19,500
- Range: TeSys
- Component type: Differential thermal overload relay
- Device short name: LRD
- Net weight: 0.375 kg
- Relay application: Motor protection
- Network type: DC / AC
- Thermal overload class: Class 10A conforming to IEC 60947-4-1
- Thermal protection adjustment range: 30…40 A
Additional information
| Setting Range | 30…40A |
|---|
Product Specifications
|
Device short name
|
lrd
|
|
relay application
|
motor protection
|
|
network type
|
dc / ac
|
|
net weight
|
0.375
|
|
thermal overload class
|
class 10a conforming to iec 60947-4-1
|
|
thermal protection adjustment range
|
30…40 a
|
|
rated insulation voltage [ui]
|
power circuit; 600 v conforming to csa / power circuit; 600 v conforming to ul / power circuit; 690 v conforming to iec 60947-4-1
|
|
for use with contactors lc1
|
d40 ~ d65
|
|
network frequency
|
0…400 hz
|
|
mounting support
|
plate, with specific accessories rail, with specific accessories under contactor
|
|
tripping threshold
|
1.14 +/- 0.06 ir conforming to iec 60947-4-1
|
|
auxiliary contact composition
|
1 no + 1 nc
|
|
conventional free air thermal current [ith]
|
5 a for signalling circuit
|
|
permissible current
|
0.95 a at 380 v ac-15 for signalling circuit / 0.06 a at 440 v dc-13 for signalling circuit
|
|
rated operational voltage[ue]
|
690 v ac 0…400 hz for power circuit conforming to iec 60947-4-1
|
|
associated fuse rating
|
4 a gg for signalling circuit, 4 a bs for signalling circuit
|
|
rated impulse withstand voltage [uimp]
|
6 kv
|
|
phase failure sensitivity
|
tripping current 130 % of ir on two-phase, the last one at 0
|
|
control type
|
red push-button stop, blue push-button reset
|
|
temperature compensation
|
-20…60 °c
|
|
climatic withstand
|
conforming to iacs e10
|
|
ip degree of protection
|
ip20 conforming to iec 60529
|
|
ambient air temperature for operation
|
-20…60 °c without derating conforming to iec 60947-4-1
|
|
ambient air temperature for storage
|
-60…70 °c
|
|
flame retardance
|
v1 conforming to ul 94
|
|
mechanical robustness
|
shocks; 15 gn for 11 ms conforming to iec 60068-2-7, vibrations; 4 gn conforming to iec 60068-2-6
|
|
dielectric strength
|
1.89 kv at 50 hz conforming to iec 60947-1
|
Product Details
TeSys LRD thermal overload relay, 40A/690V, thermal setting range 30-40A, tripping class 10A, for protection of 3-phase motors 18.5kW@400V. Differential device with phase failure and load unbalance detection. It provides a thermal adjustment dial, a manual-automatic reset selector, a test selector for simulation of tripping, reset, and stop buttons, a flag indicator, and 2 auxiliary contacts 1NO+1NC for fault signaling. Settings are protected by a transparent cover lockable by sealing. Connection by EverLink BTR screw terminals, it connects directly to the bottom terminals of 3-pole contactors LC1D40A-D80A. Mounting on DIN rail or screw fixing, separated from the contactor, with the use of a terminal block LAD96560 (to be ordered separately). Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHs/Reach).







Reviews