Schneider GV2ME14 3 Pole 6…10A Motor Protection Circuit Breaker

 16,000
 12,000

  • Range: TeSys Deca
  • Product name: TeSys GV2 / TeSys Deca
  • Net weight: 0.26 kg
  • Device short name: GV2ME
  • Component type: Motor circuit breaker
  • Device application: Motor protection
  • Poles description: 3P
  • Rated current [In]: 10 A
  • Network type: AC
  • Utilisation category: Category A conforming to IEC 60947-2

Additional information

Thermal Trip Range

6.0…10A

No of Pole

3 Pole

Product Specification

Range
tesys deca
product name
tesys gv2 / tesys deca
product or component type
motor circuit breaker
net weight
0.26 kg
device short name
gv2me
device application
motor protection
trip unit technology
thermal-magnetic
poles description
3p
network type
ac
utilisation category
category a conforming to iec 60947-2
network frequency
50/60 hz conforming to iec 60947-4-1
35 mm symmetrical din rail
clipped
panel
screwed (with adaptor plate)
breaking capacity
100 ka icu at 230/240 v ac 50/60 hz conforming to iec 60947-2
control type
push-button
rated current [in]
10 a
thermal protection adjustment
46…10 a conforming to iec 60947-4-1
magnetic tripping current
138 a
conventional free air thermal current [ith]
10 a conforming to iec 60947-4-1
rated operational voltage [ue]
690 v ac 50/60 hz conforming to iec 60947-2
rated insulation voltage [ui]
690 v ac 50/60 hz conforming to iec 60947-2
rated impulse withstand voltage [uimp]
6 kv conforming to iec 60947-2
phase failure sensitivity
yes conforming to iec 60947-4-1
suitability for isolation
yes conforming to iec 60947-1 § 7-1-6
power dissipation per pole
2.5 w
mechanical durability
100000 cycles
electrical durability
100000 cycles for ac-3 at 415 v in / 100000 cycles for ac-3e at 415 v in
standards
en/iec 60947-2 / en/iec 60947-4-1
ik degree of protection
ik04
ip degree of protection
ip20 conforming to iec 60529
climatic withstand
conforming to iacs e10
ambient air temperature for storage
-40…80 °c
fire resistance
960 °c conforming to iec 60695-2-11
ambient air temperature for operation
-20…60 °c
operating altitude
2000m

Product Details

TeSys GV motor circuit breaker, 3 poles (3P), 10A/690V, for 3-phase motor applications 3-4kW@400V. It provides a thermal-magnetic protection with a thermal setting range 6-10A, magnetic tripping at 13xIn, high breaking capacity Icu 100kA@400V. Connection by screw clamp terminals. Start-stop control by push-button guaranteed for 100 000 cycles AC-3. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine, ATEX), Green Premium compliant (RoHS/REACh).

User Manual

Schneider_Electric_TeSys-Deca-Manual-Starters-and-Protectors-GV2_GV2ME14

schneider-gv2me14-3p-mpcb-breaker